Please click on one of the questions below to view its answer.
Form of Separation/Construction
IP Ratings
Short Circuit rating
-
What is the prospective short circuit rating of my transformer?
No. of Transformers & Rated Output Rated Current Transformer Total Available Current Max. Prospective Short-Circuit Current [kVA] [A] [A] [kA] 1 x 500
2 x 500722
722722
144418.0
36.01 x 630
2 x 630
3 x 630910
910
910910
1820
273022,7
45.4
68.11 x 800
2 x 800
3 x 8001156
1156
11561156
2312
346823,1
46.2
69.31 x 1000
2 x 1000
3 x 10001444
1444
14441444
2888
433228,9
57.8
86.71 x 1250
2 x 1250
3 x 12501805
1805
18051805
3610
541536,1
72.2
108.31 x 1600
2 x 1600
3 x 16002312
2312
23122312
4624
693637.0
74.0
111.01 x 2000
2 x 20002890
28902890
578046,2